Banner U-Gage Ultrasonic Sensor Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para não Banner U-Gage Ultrasonic Sensor. Banner U-GAGE T30U Series Sensors Pump-In/Pump-Out Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 8
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
Ultrasonic Sensors with Pump-In/Pump-Out Switching Logic
ULTRASONIC
Fast, easy-to-use TEACH-Mode programming; no potentiometer adjustments
Program both outputs together or independently. The two outputs may be identical, independent,
overlapping, or complementary
Remote TEACH for security and convenience
Choose models with 150 mm to 1 m range (5.9 in to 39.4 in) or 300 mm to 2 m range (11.8 in to 78.7
in)
Wide operating range of -20° to +70°C (-4° to +158°F)
Choose models with either NPN or PNP dual discrete outputs
LED indicators for Power ON/OFF, Signal Strength, and Discrete Outputs Conducting
Choose models with integral unterminated 2 m (6.5 ft) or 9 m (30 ft) or with Euro-style QD connector
Compact, self-contained, right-angle sensor package with fully encapsulated electronics
Rugged design for use in demanding sensing environments; rated IEC IP67, NEMA 6P
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious injury or death. This
device does NOT include the self-checking redundant circuitry necessary to allow its use in personnel safety applications. A sensor
failure or malfunction can cause either an energized or de-energized sensor output condition.
Models
Models Range and Frequency Cable Supply Voltage Discrete Output Response Time
T30UHNA
T30UHNAQ
150 mm to 1 m
(5.9 in to 39 in)
228 kHz
2 m (6.5 ft)
5-pin Euro QD
12 to 24V dc
NPN (sinking)
48 ms
T30UHPA
T30UHPAQ
PNP (sourcing)
T30UHNB
T30UHNBQ
300 mm to 2 m
(11.8 in to 79 in)
128 kHz
NPN (sinking)
96 ms
T30UHPB
T30UHPBQ
PNP (sourcing)
Overview
U-GAGE® is an easy-to-use ultrasonic sensor, ideal for demanding environments. Simple push-but-
ton programming provides flexibility for a variety of applications. Excellent for gauging applications
such as sensing liquid levels in a tank or for sensing most clear materials.
Each sensor includes two discrete outputs, which may be programmed independently with different
window limits or together with identical limits.
Pump-In/Pump-Out Switching Function
Pump-in/pump-out operation provides the switching logic required for fill-level control, web tensioning
control, and similar applications. In this mode, Output 2 energizes when the target reaches the far-
thest sensing window limit, and stays energized until the target moves to the nearest limit. Output 1
de-energizes at the farthest limit and does not re-energize until the target moves to the nearest limit.
Figure 2 shows how pumping action might be controlled directly by the sensor in a fill-level-control
application.
Green Power ON/OFF LED
Yellow Output 1 LED
Red Signal Strength LED
Output 1
Programming Push Button
Yellow Output 2 LED
Output 2
Programming Push Button
U-GAGE
WHITE
1 2
POWER SIGNAL
OUTPUT
DUAL
DISCRETE
BLACK
U-GAGE
WHITE
1
2
POWER SIGNAL
OUTPUT
DUAL
DISCRETE
BLACK
Output 1 = Pump-Out
Output 2 = Pump-In
Figure 1. Sensor features
1
9 m (30 ft) cables are available by adding suffix W/30 to the model number of any cabled sensor (for example, T30UHNA W/30). A model with a QD connector requires an optional mating
cable; see Cordsets on page 7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
U-GAGE® T30U Series Sensors - Pump-In/Pump-Out
Vista de página 0
1 2 3 4 5 6 7 8

Resumo do Conteúdo

Página 1 - Overview

Ultrasonic Sensors with Pump-In/Pump-Out Switching Logic ULTRASONIC • Fast, easy-to-use TEACH-Mode programming; no potentiometer adjustments• Progra

Página 2 - Sensor Programming

High Level (Near Limit)Pump-in Output 2(Black Wire)Pump-out Output 1(White Wire)Low Level (Far Limit)Initial Level1 Initial Tank Level - Output is INA

Página 3 - >2 sec

Teaching Separate Window Limits for Each OutputEach output conducts in its respective manner (either pump-in or pump-out) independently, in re-sponse

Página 4

Program Second OutputRepeat as needed for other output.Teaching Identical (Complementary) Window Limits for Both OutputsA Single Pair of Sensing Windo

Página 5 - Specifications

Push Button LockoutPush ButtonRemote Wire0.04 sec. < T < 0.8 sec.Procedure Result Procedure ResultNot available via push but-tonNot applicable•

Página 6 - Performance Curves

Output ProtectionProtected against continuous overload and short-circuit; transient over-voltage; no false pulse on power-upOutput Response Time“A” su

Página 7 - Dimensions

Dimensions M30 x 1.5Threadø 40.0 mm(1.57")Cabled Models Quick-Disconnect ModelsJam Nut(Supplied)45.0 mm(1.77")ø 15 mm(0.59")11.5 mm(0.4

Página 8 - Brackets

BracketsAll measurements are in mm.SMB30A•Right-angle bracket with curvedslot for versatile orientation• Clearance for M6 (¼ in) hardware• Mounting ho